P&C Protection & Control

GSM-RTU / GSM-16

AutoLog® GSM-16 RTU.

The recommended GSM-RTU for pump stations, water-utility SCADA and unattended industrial sites. Built-in GSM/GPRS modem, up to twenty digital inputs, four 5 A relay outputs and up to eight freely-configurable analog channels — 4..20 mA, Pt100, KTY10, NTC, voltage or RMS measurement, selectable per point. Programmed in AutoLog GsmProgrammer; communicates via SMS, GPRS, Modbus RTU/TCP. Made in Finland, verified operating range −30 to +70 °C.

Specification

Features and specifications.

Specifications below are taken directly from the AutoLog® GSM-16 RTU datasheet.

AutoLog® GSM-16

Pump-station-class GSM-RTU · Built-in GSM/GPRS modem

Pump-station-class GSM-RTU combining standard PLC features with a built-in GSM/GPRS/SMS modem. Four digital inputs (max 20 with AI2DI modules), four relay outputs and up to eight analog inputs with freely-selectable plug-in modules per point. Two serial ports — RS485 and Ethernet available as plug-in modules. Communicates via SMS, GPRS, Modbus RTU master/slave or Modbus TCP. Connects to AutoLog® Wireless I/O & Sensors and any AutoLog® HMI. Programmed in AutoLog GsmProgrammer with 512 programming lines, built-in PID controllers, FTP data logging and advanced SMS generation.

Inputs & outputs

Analog inputs
0–8× 12-bit (0–4000), freely-selectable per point: 4..20 mA, 4..20 mA isolated, Pt100, KTY10, NTC, 0..5/10 V, ±10 V, RMS AC
Digital inputs
4× 24 VDC, opto-isolated, PNP, max 8 mA (up to 20 with AI2DI modules)
Relay outputs
4× 5 A / 250 VAC, 1 A / 30 VDC
HMI support
Keypad & LCD via I²C; touch screen via serial port 2 (Modbus)

Communication

Serial port 1
RS232 (GSM modem / programming), RJ45, 9600 bps
Serial port 2
RS232 / opt. RS485 / opt. Ethernet (plug-in)
Protocols
Modbus RTU master/slave, Modbus TCP, SMS, GPRS
Speed
300–57600 bps
GSM/GPRS
Built-in modem, SMA antenna (internal or external)

Power

Powering
12–30 VDC / 12–24 VAC; ext. 230/110 VAC available
Power output
12/24 VDC for accessories, optional over-charge protector

Programming & memory

Programming
AutoLog GsmProgrammer (Windows), 512 lines, PID, FTP, RTC
Battery backup
RTC + calendar + program memory
Storage
Flash memory for application + data
Indicators
LEDs for Rx/Tx, GSM modem, DI/DO, RUN
Switches
4 jumpers + 6 DIP switches

Environmental

Operating range
−30 to +70 °C
Storage range
−40 to +80 °C
Humidity
95% non-condensing
EMC immunity
EN 50082-1 / EN 50082-2
EMC emissions
EN 50081-1 / EN 50081-2

Physical

CPU card size
220 × 125 × 65 mm, 0.3 kg
Enclosure
Optional, up to IP68. ABS / Polycarbonate / Stainless steel. Wall, pole, ATEX options.
Made in
Finland

Specify GSM-16 in your project

Need the GSM-16 for a specific application?

We can supply the GSM-16 as a bare CPU card, mounted in a customer-specified enclosure, or as a complete commissioned RTU package. Bulk OEM orders welcome — multi-year cooperation agreements are how we have shipped tens of thousands of units.

Request GSM-16 quote