P&C Protection & Control

OEM-PLC / AL-14LP

AutoLog® AL-14LP PLC.

Low-Power AutoLog® OEM PLC designed for off-grid installations. Operates from a 12 / 24 VDC accumulator rechargeable by solar panel or exchanged in the field. Four configurable power-save modes — Run (5.6 – 20 mA), Idle (2.2 mA, clock + DI + serial wake), Stop (1.2 mA, clock + DI wake) and Clock-interruption (140 µA) — let the application program the controller's standby behaviour at remote sites. Eight digital inputs, eight digital outputs plus one PNP output for external sensor powering, zero-to-four analog inputs and two serial ports. Each interface (AI, I²C, serial) can be individually power-gated. Made in Finland, verified operating range −30 to +70 °C.

Specification

Features and specifications.

Specifications below are taken directly from the AutoLog® AL-14LP PLC datasheet.

AutoLog® AL-14LP PLC

Low-Power OEM-PLC · battery + solar · 4 power-save modes

Designed for remote, off-grid sites: pumping stations beyond the mains, environmental monitoring buoys, solar-powered telemetry on pipelines. Eight digital inputs, eight digital outputs (NPN) plus one PNP output dedicated to powering external sensors only when the program needs them, zero-to-four 12-bit analog inputs with the standard AutoLog plug-in module catalogue, two serial ports. Same 512 kB FLASH / 8 000-line / 32-PID program capacity as the rest of the family. The standout feature is the four-mode power state machine — at 140 µA clock-interruption draw, a single 12 V accumulator can run the AL-14LP for years between charges.

Inputs & outputs

Digital inputs
8× 12/24 VDC, max 8 mA, PNP, opto-isolated
Digital outputs
8× NPN + 1× PNP (external sensor power), 12/24 VDC max 1 A (group max 4 A), opto-isolated
Analog inputs
0–4× 12-bit plug-in modules: Pt100 (−50..150 / 0..500 / −250..750 °C), KTY10, NTC, 0..2/5/10 V, ±10 V, 0..5/20 mA, 4..20 mA, RMS 40/25/0.25 VAC. Power to AI bank can be closed when not used
I²C port
1× HMI, iButton. Power to I²C port can be closed when not used
HMI interface
Character displays to Windows-CE touch screens via I²C or serial port

Communication

Serial port 1 (SER1)
RS232 (RJ45). Power to serial ports can be closed when not used
Serial port 2 (SER2)
RS232 (RJ45)
Modbus RTU
Master/Slave on both serial ports simultaneously, 300–115 200 bps
Remote programming
Over any Modbus-supporting medium (radio, GSM data, RS-485)

Power

Powering
12/24 VDC or 10/18 VAC, max 5 VA
UPS connector
Yes (via AL-UPS card)
Power-save: Run
5.6 – 20 mA, depends on powered hardware (AI, I²C, serial ports, LEDs, external power)
Power-save: Idle
2.2 mA — wake on clock, digital input or serial port interruption
Power-save: Stop
1.2 mA — wake on clock or digital input interruption
Power-save: Clock-interruption
140 µA — wake on clock only

Programming & memory

Programming tool
AutoLog® ALProWin — instruction list & ladder, symbolic names, trends, monitoring tables
Application memory
512 kB FLASH, 8 000 programming lines
Instructions
260+ functions
PID controllers
32 built-in
Data memory
512 kB RAM
Data logging
E.g. 10 time-stamped measurements × 3 000 records
Clock / calendar
Built-in (remotely settable)
Battery backup
Yes

Physical & environmental

Operating range
−30 to +70 °C
Storage range
−40 to +80 °C
EMC immunity
EN 50082-1 / EN 50082-2
EMC emissions
EN 50081-1 / EN 50081-2
Enclosure
Default DIN-rail metal cover (IP20); optional IP65 plastic box or metal box
Size
225 × 125 × 65 mm, ≈ 0.3 kg
Made in
Finland

Order code

AL14LP
900670 (AutoLog® 14LP PLC)

Specify AL-14LP in your project

Need a solar-powered or battery-run remote controller?

We can supply the AL-14LP as a bare CPU card or as a complete solar-powered cabinet with accumulator, charge controller and antenna. Multi-year off-grid SCADA deployments are part of our delivery history.